Gate Valve

Gate Valves function is to isolate or sectionalize any piece of equipment or length of pipeline in water or sewage systems.

It is normal practice, therefore, to use them on a suction and delivery branches of pumps at regular intervals along a pipeline, at branches underneath air valves, on bye-passes, on drains or washouts etc.

They have a low head loss coefficient, hence are ideal on pump installations to maximize system efficiency.

Technical Information


Maximum Unbalanced Head for Manual Operation of inside screw gate valves

Valve Bore (mm)

Headwheel Dia (mm)

Unbalanced Head (m)



Handwheel Operation

Tee Key Operation

80

200

140

160

160

100

250

105

160

160

150

250

105

160

160

200

300

40

73

140

250

400

40

50

93

300

400

30

35

65

350

533

12


17

400

610

10


13

450

686

8


10

500

686

7


8

600

762

3


3

  • . Max input effort is 50kg ( 25kg Push/Pull )
  • Tee Key has 0.7m arm (0.6m effective length )
  • For greater unbalanced head it is necessary to use a bypass or fit totally enclosed units having integral ball bearing collar.